Anak Agung, Anak Agung Bayu Amertha ANALISIS KESESUAIAN ALAT PEMADAM API RINGAN SEBAGAI SISTEM PROTEKSI KEBAKARAN AKTIF DI ASRAMA POLITEKNIK PENERBANGAN INDONESIA CURUG. Jurnal Review Pendidikan dan Pengajaran. (Unpublished)
PKP17_ANAK AGUNG BAYU AMERTHA_TUGAS AKHIR_2026.pdf
Restricted to Registered users only
Download (2MB) | Request a copy
Abstract
Penelitian ini dilatarbelakangi oleh pentingnya Alat Pemadam Api Ringan(APAR) sebagai sistem proteksi kebakaran aktif untuk mengendalikan kebakaran pada tahap awal di lingkungan asrama. Hasil observasi awal menunjukkan masih terdapat ketidaksesuaian pada jumlah, penempatan, kondisi fisik, dan pemeliharaan APAR di Asrama Politeknik Penerbangan Indonesia Curug. Penelitian ini bertujuan menganalisis tingkat kesesuaian APAR berdasarkan jumlah, penempatan, pemasangan, dan pemeliharaan sesuai ketentuan yang berlaku serta menganalisis dampak ketidaksesuaian tersebut terhadap fungsi APAR sebagai sistem proteksi kebakaran aktif. Penelitian
menggunakan metode evaluatif dengan pendekatan kualitatif. Data dikumpulkan melalui observasi, wawancara, dan dokumentasi, kemudian dianalisis dengan mengevaluasi kondisi aktual APAR berdasarkan ketentuan yang menjadi acuan penelitian. Hasil penelitian menunjukkan bahwa luas bangunan asrama sebesar 7.599 m² memerlukan 44 unit APAR, sedangkan yang tersedia hanya 8 unit sehingga masih terdapat kekurangan 36 unit. Selain itu, distribusi APAR belum merata, beberapa APAR mengalami korosi dan tekanan tidak normal, serta pemeriksaan berkala belum dilaksanakan secara optimal. Ketidaksesuaian tersebut berdampak pada menurunnya kesiapsiagaan penghuni, terhambatnya penanganan kebakaran pada tahap awal, dan berkurangnya efektivitas APAR sebagai sistem proteksi kebakaran aktif. Disimpulkan bahwa kondisi APAR belum memenuhi ketentuan yang berlaku sehingga diperlukan perbaikan jumlah, penempatan, dan pemeliharaan APAR.
This study was motivated by the importance of portable fire extinguishers (APAR) as an active fire protection system for controlling fires at an early stage in dormitory buildings. Preliminary observations indicated non-compliance in the number, placement, physical condition, and maintenance of portable fire extinguishers at the dormitory of the Indonesia Civil Aviation Polytechnic Curug. This study aimed to analyse the compliance of portable fire extinguishers in terms of quantity, placement, installation, and maintenance based on the applicable regulations, as well as to examine the impact of such non-compliance on their function as an active fire protection system. The study employed an evaluative research method with a qualitative approach. Data were collected through observation, interviews, and documentation, then analysed by evaluating the actual condition of the extinguishers against the applicable criteria. The results showed that the 7,599 m² dormitory required 44 portable fire extinguishers, while only 8 units were available, leaving a shortage of 36 units. In addition, extinguisher distribution was uneven, several units showed corrosion and abnormal pressure, and periodic inspections had not been optimally implemented. These deficiencies reduced occupant preparedness, hindered initial fire suppression, and decreased the effectiveness of portable fire extinguishers as an active fire protection system. It is concluded that the existing conditions do not meet the applicable requirements, highlighting the need to improve the quantity, placement, and maintenance of portable fire extinguishers.
| Item Type: | Article |
|---|---|
| Uncontrolled Keywords: | Sistem proteksi kebakaran aktif, alat pemadam api ringan, kesesuaian APAR, keselamatan kebakaran, asrama. active fire protection system, portable fire extinguisher, fire extinguisher compliance, fire safety, dormitory. |
| Subjects: | H Social Sciences > HE Transportation and Communications |
| Divisions: | DIII Pertolongan Kecelakaan Pesawat |
| Depositing User: | Mr. Anak Agung Bayu Amertha - |
| Date Deposited: | 19 Aug 2026 03:43 |
| Last Modified: | 19 Aug 2026 03:43 |
| URI: | http://repository.ppicurug.ac.id/id/eprint/937 |